4 DUALINTERFACEOPERATION
Whenoperatingacontroller(readingmeasuredvalueandsendingsetpoint)forproperoperationitisimportantthat
thecontroller getsits setpoint fromtheright source.Setpointsmaycomefromdifferentsources:analog input, field
businterfaceorRS232ormaybeoverruledbyclosevalveoropenvalve(purge)
commands.Thereforeitisimportant
toknowwhatthesetpointsourceofthecontrolleris.Thiscanbesetbymeansofparametercontrolmode(process1,
parameter4).
Insomecasesitispossiblethatthesetpointsmaycomefrom2sourcesatthesametime.Thelastsend
setpointwill
bevalidandsendtothecontroller.Thisisthecaseincontrolmode=0,whensetpointsmaycomethroughanyfield
businterfaceorRS232.
However,there could be situations where control over the instrument seems impossible. This is the case when the
instrument comes into a
safestate e.g. when field bus communication is disturbed or disconnected. Valve will be
forcedtoasafestateautomatically:closed(NC)orfullyopen(NO).
IncaseyouwanttogetcontrolbackviaRS232operation,youhavetochangethecontrolmode.Whencontrolmode
getsvalue18,
safestatewillbeoverruledandsendingsetpointsviaRS232interfacewillhaveeffectonthecontroller
again.
Seealsodocumentnr.9.17.023formoredetaileddescriptionaboutdigitalinstrumentparametersand
theirbehaviour.