BRONKHORST®
Page20RS232interface 9.17.027
CommunicationcanbeclosedandinterfacecanbedisabledfromFLOW‐BUStoken‐ringtrafficbysendingthe
commandbelowviatheRS232totheinterface.
StopcommunicationRS232interface
Send Comment
:050101001101\r\n closecommunicationinstruction forinterfacemoduletherewillbenoanswer(because
communicationstops)secondbyteisactualnodeaddressforinterface(here:01)
3.10 EXAMPLES
3.10.1 Sendingsetpoint
Sendsetpoint=50%tonode3process1.Setpointvaluesshouldbegiveninarangefrom0to32000soforthis
example16000shouldbesend.
Sendsetpoint=50%tonode3process1parameter1
Nr Byte Layout Description Descriptionperblock
0 :Startcharacter
Start
1 06Length6
2 03Node3
3 01Commandwritewithstatusresponse
4 01
cppppppp
00000001
c 00 Processnotchained
Process1
p 01 Process1
5 21
cttppppp
00100001
c 00 Parameternotchained
Parameternumber1
Setpoint
t 20 Parametertype‘integer’
p 01 Parameternumber(FBnr.)1
6 3E
Setpoint16000=3E80h
7 80
8 \rCarriageReturn
End
9 \nLineFeed
TotalString :06030101213E80\r\n
Answerfromnode3
Nr Byte Description Descriptionperblock
0 : Startcharacter
Start
1 04 Fixedmessagelength4.
2 03 Nodeaddress03
3 00 Commandstatus
4 00 Statusok.
Statusanswer
5 05 Statusok,valuepointstoendofsendmessage.
6 \r CarriageReturn
End
7 \n LineFeed
TotalString :0403000005\r\n
Positionofnr5isasfollows.
String : 06 03 01 01 21 3E 80 \r\n
Position 1 2 3 4 5 6