BRONKHORST®
Page8DeviceNetinterface 9.17.026
2 FIELDBUSINSTALLATION
2.1 GENERAL
This chapter introduces the DeviceNet cable system and provides a brief overview of how to set up a DeviceNet
networkefficiently.Thestepsinthischapterdescribethebasictasksinvolvedinsettingupanetwork.
FortheinstallationofDeviceNet,ODVAhascreatedadocumentwhichcanbefoundintheDeviceNet
library:
PUB00027R1_Cable_Guide_Print_Copy.pdf
2.2 DEVICENETCONNECTOR
Bronkhorstinstrumentsarefittedwithamicro‐stylesealedM12connector.
M12Connector Male Female nr Color
Wire
Identity
Usage
Round
1 Bare Drain shield
2 RED
V+
(+24Vdc)
power
3 Black
V‐
(0Vdc)
power
4 White
CAN_H
(CAN+)
signal
5 Blue
CAN_L
(CAN‐)
signal
4
2
3
5
1