3.5 DEVICECONFIGURATION
3.5.1 AvailabledatacombinationsforPolledI/O
UsingtheEDS‐fileintheDeviceNetconfigurationprogramofthemaster,followingI/Ocombinationsareavailable(IO
AssemblyInstances):
Inputs:
1. ExceptionStatus +Flowdata‐type:integer (0xC3)
2. ExceptionsStatus +Flow+Setp+Override+Valvesignal data‐type:integer (0xC3)
3. ExceptionStatus +Flowdata
‐type:float (0xCA)
4. ExceptionsStatus +Flow+Setpoint+Override+Valve data‐type:float (0xCA)
Outputs:
1. Setpointdata‐type:integer (0xC3)
2. Override+Setpointdata‐type:integer (0xC3)
3. Setpointdata‐type:float (0xCA)
4. Override+Setpointdata‐type:float (0xCA)
3.5.2 Availableparameterdata
UsingtheEDS‐fileintheconfigurationprogramofthemaster,followingparametersareavailableforcustomising:
1. PolledI/O(input) :selectIOAssemblyInstanceforinput(datacombinationpolledI/O)
2. PolledI/O(output) :selectIOAssemblyInstanceforoutput(datacomb.polledI/O)
3. Controlmode
:setscontrollertoidle,valveoff,purgeornormalsetpoint
4. Setpointramprate(msec) :setsramprateofsetpointfrom0…3000000msec
5. Fluidnumber:selectswantedcalibration/fluidnr.:1…8
6. Alarm :switchesalarmsonoroff
7. Alarmdelay(msec) :setsalarmdelay
timeinrange0…65000msec
Parameter"PolledI/O(input)"and"PolledI/O(output)"mustalwaysbesettothecorrectvalue.This
willselectthedatacombinationforPolledI/O(IOAssemblyInstance).Ifitisnotpossibletostart
communicationwiththedevicealwayscheckthesetwosettings!