4 FLOWBUSINSTALLATIONANDADDRESSING
4.1 INSTALLATION
AllmodulesinaFLOWBUSsystemmusthavetheirownaddress.FLOWBUSsystemswillnotfunctionproperlywhen
thereare more modulesonthesameaddress.Toavoidthis, modules willdoacheckbeforegettingoperationalon
theirbusaddressandgiveamessagewhenthisaddressisoccupied.Ifyoure
ceiveacompleteFLOWBUSsystemfrom
Bronkhorstallmoduleshavebeen installedtothebusalready(inonesystem).Eachtimeyoupowerupyoursystem
afterwards,themoduleswillstartuponthesameaddressonthebus,becausethesesettingsarestoredintheirnon
volatile memo
ry. So if you receive a new system, normally you only have to connectthe cables and switch on the
power.
Page19
FLOWBUSinterface9.17.024
Seedocument9.17.023foramoreinformation.
Thisdocumentcanbefoundat:
http://www.bronkhorst.com/en/downloads
/instruction_manuals/
If a new module has to be connected to a bus system, it needs a free address. Normally this will be the first free
address counted from address 3. Address 0 is reserved for the startup procedure. Address 1 is reserved for an
interfacemoduleto(personal)computersandaddress2hasbee
nreservedforoperationmoduleslikeE7000.There
arefourwaystoaddanewmoduletoyourbussystem:
4.1.1 Installtobusviarotaryswitchesonthesideoftheinstrumen t(if present).
Onthesideoftheinstrumentarerotaryswitchesplacedandalabelwiththe
explanationoftheswitches.Makesuretouseascrewdriverwhichissuited
fortheswitches.
Theswitcheshavethefollowingfunction:
NODEADDRESS(0099)
WiththeNODEADDRESSswitch,theinstrumentsaddresscanbeset.TheMS
Disthehighpartofthedecimalnumber
andtheLSDthelowpart.Forinstanceaddress25meansMSDon2andLSDon5.
Thedefaultswitchpositionis00.Inthispositiontheaddressissoftwareprogrammable.
Thedefaultsoftwareprogrammableaddressis3.
Durin
ginstrumentinitialisation,thenodeaddressswitchesareread.IftheswitchesspecifyavalidFLOWBUSaddress,
i.e.avaluefro
m3to99,thisvalueisused.
Ifthespecifiedaddressdiffersfromthevaluestoredintheinstrument,thenewaddressissavedinmemory.
IftheswitchesspecifyaninvalidFLOWBUSaddress,i.e.avalueof1or2,thevaluestoredintheinstr
ument’smemory
willbeusedastheaddress.
4.1.2 AutomaticinstallationtoFLOWBUS
MostFLOWBUS moduleshave thefacilityto install themselvesautomatically onthe bus.This meansthattheyare
abletofindthefirstfreenodeaddresscountedfrom3andconnectthemselvestothebus.Thisactioncanbestarted
bymeans of a manual interface on themodule. Directlyafterwards the newmodule will be part of the FLOWBU
S
system.
Makesuretoinstallonlyonenewmoduleatthesametime.